SYMBOL STRUCTURE

KRUN - X - X - XX Y1

Outdoor complete switchgears

Rated voltage of the higher side voltage 6 or 10 kV

Designation of the main circuit diagram (according to table 3)

High - voltage input and output (in - air, to - cable)

Climatic modification and category of placement according to GOST 15150 - 69.

TERMS OF USE

The nominal value of climatic factors is according to GOST 15150 - 69.

Height above sea level - no more than 2000 m.

The degree of pollution of the atmosphere I . . . III.

Group of operating conditions in terms of the impact of mechanical factors of the external environment - M3

according to GOST 17516.1 - 90.

Safety requirements in accordance with GOST 12.2.007.4 - 75.

TECHNICAL DATA

Rated voltage on the high voltage side (HV), kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 10

The highest operating voltage on the HV side, kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7,2,12

Rated current of main circuits KRUN, A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400, 630, 1000

Rated current of the busbars, A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400, 630, 1000

Rated breaking current of the circuit breaker built into KRUN, kA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Thermal withstand current (short - term current), kA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . twenty

Rated current of electrodynamic resistance of the main circuits of KRUN (amplitude), kA . . . . 10,16,21,

26, 32, 41, 51, 64, 81,102, 128, 161, 204, 255, 320

Thermal resistance current flow time, s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Rated supply voltage of auxiliary circuits, V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100, 220

Rated voltage of lighting circuits, V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Service life, years . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . fifteen

CONTENTS OF DELIVERY

KRUN with equipment and devices of the main and auxiliary circuits in accordance with the questionnaire

Operational documents, 1 copy

Spare parts and accessories, set according to specification on order

Note:

delivery is carried out disassembled (KRUN and explosive tower are transported separately); when transported over long distances, the measuring instruments can be removed and stored in separate boxes.